Modular Building Controller/Remote Building Controller (MBC/RBC)
180
| 231
125-3002
Digital Output
WARNING
- High and low voltage cannot be combined on the same PTM.
- A 2Q250-M PTM must have 24 Vac voltage fed into the M-Bus.
- Circuits powering a PTM6.2Q250-M must be limited by a 15-amp (max.) circuit
breaker.
Fig. 133: Connecting a Digital Output (Latched or Pulsed).
LFSSL (Logical FAST/SLOW/STOP Latched)
WARNING
For points defined as LFSSL, DO NOT use the PTM6.2Q250-M.
Fig. 134: Connecting an LFSSL (No Proof).