Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Modular Building Controller/Remote Building Controller (MBC/RBC)
178
| 231
125-3002
Digital Input
Fig. 130: Connecting a Digital Input (Dry Contacts).
1. A single common may be used for all digital inputs on the same point termination
module.
2. Excitation equals 22 Vdc at 8 mA. Pulse rate equals 25 Hz.
3. Dry contact only. Does not require gold contacts.
4. Solid state device must be rated for 30V minimum, with RDS on less than 200
ohms and RDS off greater than 50K ohms.
WARNING
High and low voltage cannot be combined on the same PTM.