PTM Wiring Diagram Reference.
Point Type Specifics PTM Qty PTM Type Diagram
Sensing)
WARNING:
High and low voltage cannot be combined on the same PTM.
Logical Pulsed Accumulator
1 – DI (Counting)
Pulse accumulating for counting pulses initiated by
dry contact.
1 2C
Connecting a
Digital Input
(Pulse
Accumulation
)
Logical Digital Output
1 – DO
DO latched or pulsed 1 or
1
2Q250 or 2Q250-
M
Connecting a
Digital Output
(Latched or
Pulsed)
WARNING:
High and low voltage cannot be combined on the same PTM.
A 2Q250-M PTM must have 24 Vac voltage fed into the M-Bus.
CAUTION:
Circuits powering PTM6.2Q50-M point modules must be limited by a 15-amp (max.) circuit breaker.
Logical FAST/SLOW/ STOP
Latched Control
1 – DO (OFF/Fast)
1 – DO (OFF/SLOW)
1 – DI (Proof)
LFSSL (no proof) 1 2Q250 Connecting
an LFSSL
(No Proof)
LFSSL (proof of contact) 1
1/2, or
1/4
2Q250
2D20, or
4D20
Connecting
an LFSSL
(Proof of
Contact)
LFSSL (proof of voltage) 1
1/2
2Q250
2D250
Connecting
an LFSSL
(Proof of
Voltage)
Logical FAST/SLOW/STOP Pulsed
Control
1 – DO (OFF)
1 – DO (FAST)
1 – DO (SLOW)
1 – DI (Proof)
LFSSP (no proof) 1-1/2 2Q250
Connecting
an LFSSP
(No Proof)
LFSSP (proof of contact) 1-1/2
1/2, or
1/4
2Q250
2D20, or
4D20
Connecting
an LFSSP
(Proof of
Contact)
LFSSP (proof of voltage) 1-1/2
1/2
2Q250
2D250
Connecting
an LFSSP
(Proof of
Voltage)
Logical ON/OFF/AUTO Latched
Control
1 – DO (ON/OFF)
1 – DO (AUTO)
1 – DI (Proof)
LOOAL (no proof) 1 2Q250 Connecting
an LOOAL
(No Proof)
LOOAL (proof of contact) 1
1, or
1/2
2Q250
2D20, or
4D20
Connecting
an LOOAL
(Proof of
Contact)
LOOAL (proof of voltage) 1
1/2
2Q250
2D250
Connecting
an LOOAL
(Proof of
Voltage)