Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Modular Building Controller/Remote Building Controller (MBC/RBC)
168
| 231
125-3002
NOTE:
UL-recognized wire (labeled with a backwards “RU”) is not field-installable. Use only
UL-listed wire.
Power Source Requirements
Power Source Requirements for MBC/RBC
Product Input Voltage Line Frequency Maximum Power
MBC 24/40 – 115V 115 Vac 50/60 Hz 200 VA
4
MBC 24/40 – 230V 230 Vac 50/60 Hz 175 VA
RBC – 115V 115 Vac 50/60 Hz 150 VA
4
RBC – 230V 230 Vac 50/60 Hz 135 VA
Power Open Processor 24 Vac ±20% 50/60 Hz 6 VA
Open Processor 24 Vac ±20% 50/60 Hz 5 VA
Power Module 24 Vac ±20% 50/60 Hz 5 VA
PTM6.2P1K 24 Vac ±20% 50/60 Hz .25 VA
PTM6.2N100K 24 Vac ±20% 50/60 Hz .35 VA
PTM6.2U10 24 Vac ±20% 50/60 Hz .20 VA
PTM6.2I420 24 Vac ±20% 50/60 Hz 2.2 VA
PTM6.2D20
1
24 Vac ±20% 50/60 Hz .75 VA
PTM6.4D20 24 Vac ±20% 50/60 Hz 3 VA
PTM6.2D250 24 Vac ±20% 50/60 Hz .75 VA
PTM6.2C 24 Vac ±20% 50/60 Hz .75 VA
PTM6.2Y10
2
24 Vac ±20% 50/60 Hz 3.2 VA
PTM6.2Y10S 24 Vac ±20% 50/60 Hz 3.2 VA
PTM6.2Y10-M
3
24 Vac ±20% 50/60 Hz 3.2 VA
PTM6.2Y10S-M 24 Vac ±20% 50/60 Hz 3.2 VA
PTM6.2Y420 24 Vac ±20% 50/60 Hz 3.5 VA
PTM6.1PSI20-M 24 Vac ±20% 50/60 Hz 2.0 VA
PTM6.2Q250 24 Vac ±20% 50/60 Hz 2.6 VA
PTM6.2Q250-M 24 Vac ±20% 50/60 Hz 2.6 VA
1)
PTM6.2D20 is no longer available.
2)
PTM6.2Y10 has been replaced by the PTM6.2Y10S; however, both are still in use.
3)
PTM6.2Y10M has been replaced by the PTM6.2Y10S-M; however, both are still in use.
4)
Cable must be part of a Structured Cabling System (SCS).