DANGER
The Transformer Secondary Neutral (N) must be connected to the building approved
earth ground whenever transformer primary is greater than 150 Vac.
Modular Building Controller/Remote Building
Controller (MBC/RBC)
Wire Type Requirements
MBC/RBC Wire Type Requirements.
Circuit Type Class Wire Type
4
Maximum Distance
1
Conduit Sharing
2
AC Line Power Power No. 12 to No. 14 AWG THHN See NEC* Check local codes
Digital Output 1, 2
No. 14 to No. 22 AWG
TP not required, check job
specifications and local codes
Check local codes Check local codes
Digital Input 2 No. 14 to No. 22 AWG
TP not required, check job
specifications and local codes
750 ft (230 m) Check local codes
High Voltage
Digital Input
1, 2 No. 14 to No. 22 AWG
TP not required, check job
specifications and local codes
750 ft (230 m) Check local codes
Analog Input
1k Nickel or Platinum
2
No. 20 AWG TP or TSP
3
CM (FT4) or CMP (FT6)
750 ft (230 m) Check local codes
Analog Input, Thermistor 2 No. 18 to No. 20 AWG TP or TSP
3
CM
(FT4) or CMP (FT6)
750 ft (230 m) Check local codes
Analog Input, 0-10V 2 No. 18 to No. 20 AWG TP or TSP
3
CM
(FT4) or CMP (FT6)
750 ft (230 m) Check local codes
Analog Input, 4-20 mA 2
No. 18 to No. 20 AWG TP or TSP
3
CM
(FT4) or CMP (FT6)
750 ft (230 m) Check local codes
Analog Output, 0-10V 2 No. 18 to No. 20 AWG TP or TSP
3
CM
(FT4) or CMP (FT6)
750 ft (230 m) Check local codes
Analog Output, 4-20 mA 2 No. 18 to No. 20 AWG TP or TSP
3
CM
(FT4) or CMP (FT6)
750 ft (230 m) Check local codes
Analog and Digital on SCS 2 24 UTP
4
, solid or stranded 328 ft (100 m) Check local codes
*
National Electric Code.
1)
Wire length affects point intercept entry. Adjust intercept accordingly.
2)
Conduit sharing rules: No Class 2 point wiring can share conduit with any Class 1 wiring except where local codes permit. Both
Class 1 and Class 2 wiring can be run in the field panel providing the Class 2 wire is UL-listed 300V 75°C (167°F) or higher, or
the Class 2 wire is NEC type CM (FT4)(75°C or higher) or CMP (FT6) (75°C or higher). NEC type CL2 and CL2P is not
acceptable unless also UL listed and marked 300V 75°C (167°F) or higher.).
3)
Twisted Shielded Pair TSP is not required for general installation, does not affect MBC/RBC specifications, and may be
substituted where otherwise specified. TSP should be used in areas of high electrical noise (for example when in proximity to
VFDs and 100 kVa or larger motors). Where used, connect the shield drain wire to the grounding system inside enclosure.
4)
Cable must be part of a Structured Cabling System (SCS).