Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
MEC Service Boxes
125
-3002
165 | 231
Fig. 118: Wiring Diagram for 115V MEC Service Box.
DANGER
Possible shock hazard!
The power switch disables power to the control side of the MEC only. Power remains
ON at the duplex receptacle (115V version) and in the service box. Power may be
present at the field devices. To avoid injury, follow proper safety precautions.
230V Version Service Box
The 230V Service Box is also available for applications where source power is 230
Vac. The high-voltage supply enters the enclosure from the top through the right-hand
side conduit knockout. The source voltage of the MEC must be current limited to 10
amps or less, depending on the requirements of any particular installation.
A termination block for power and ground termination is provided on the wire cover for
easy connection by the electrician. The termination block comes from the factory pre-
wired to the transformer through a double pole On/Off switch and circuit breaker.
MOVs (3 x 275V) are installed on input power.