Fig. 117: PXM Wiring Diagram to use an AI as a DI.
MEC Service Boxes
One of the options for powering the TX-I/O, PXC Compact, MEC, point blocks, and
24V devices is the Service Box.
CAUTION
Do not connect inductive loads, such as drill motors, vacuum cleaners, or
compressors, to the duplex receptacle on the 115V Service Box.
Service Box Source Requirements and Outputs
Maximum Input Maximum 24 Vac Output
Service Box
Type
Input Voltage Line Frequency Transformer Service Outlets Total
1
Class
2
115V 175VA 115 Vac 50/60 Hz 1.8A 2A2 175 VA 60 VA
230V 175VA 230 Vac 50/60 Hz 0.9A N/A 175 VA 60 VA
1)
Total 24 Vac Output Power is distributed to both Class 1 Power Limited Terminations for use inside the enclosure only and a
Class 2 Termination which may be used outside the enclosure.
2)
Service outlets (115 Vac only) are restricted to continuously powered network devices (0.5A) and reserved power for laptop
computers (1.5A). Plan Branch circuit for an additional 2A per 115 Vac 24 Vac Service Box.