Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Modular Equipment Controller (MEC) and Point Expansion Module (PXM)
162
| 231
125-3002
Digital Output
Fig. 115: Connecting a Digital Output (Pulsed or Latched).
Universal Inputs
To use an AI as a DI, wire the device as follows:
1. Wire a 1/2-Watt, 3.3K-ohm resistor between the 24 Vdc sensor supply and the dry
contact to be monitored. (See the following Figures.)
2. Wire the other side of the dry contact into the signal terminal of an AI point.
3. In parallel to the first 3.3K-ohm resistor, wire a second 3.3K-ohm resistor.
4. Set the jumper for the corresponding AI to current.
5. Define the point in the Firmware as an LDI.
Fig. 116: MEC Wiring Diagram to use an AI as a DI.