Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Modular Equipment Controller (MEC) and Point Expansion Module (PXM)
125
-3002
161 | 231
Digital Input
Fig. 113: Connecting a Digital Input (Dry Contacts).
1)
A single common may be used for all digital inputs.
2)
Excitation equals 24 Vdc at 22 mA. Pulse rate equals 10 Hz.
3)
Dry contact only. Does not require gold contacts.
4)
Solid state device must be rated for 30V minimum, with RDS on less than 1K ohms and RDS off
greater than 100K ohms
Fig. 114: Connecting a Digital Input (Pulse Accumulating).