Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
Actuator Terminal Equipment Controller (ATEC) BACnet or N-Variant P1
148
| 231
125-3002
Actuator Terminal Equipment Controller (ATEC)
BACnet or N-Variant P1
Fig. 93: Power Trunk Connection to ATEC.
BACnet ATEC or N-Variant P1 ATEC (Updated Hardware) Power Source Requirements.
Product Input Voltage Line Frequency Maximum Power
1) 2) 3)
BACnet Actuator 24 Vac 50/60 Hz 5 VA + DO loads
1) Total VA rating is dependent upon the controlled DO loads (for example, actuators, contactors, and so on) and is limited
to 12 VA per DO.
2) Smoke control listed ATECs are limited to 6 VA max per DO.
3) Do not control more than the nameplate rated loads for DOs of the electronic output controllers. The controller UL and
CSA listing is based on the nameplate power rating.