Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
125
-3002
147 | 231
NOTE:
The operating supply voltage range for the KNX/PL-Link is DC 21 through 30V.
DXR2 supplies 50 mA that may not be shared. To obtain more power, shut off the
DXR2 KNX/PL-Link supply and connect up to eight JB125C23 KNX power supplies.
The devices receive power from the connected room automation station using the
KNX PL-Link Terminals +11 and 12. Calculate the voltage drop using cable
resistance in
Power Trunk Layout [ 67]. All devices must have a minimum input of
DC 21V.
KNX/PL-Link Interface Power Consumption (From Room Automation Station).
Part Number Description Maximum mA at DC 24V
QMX3.P02 Wall Temperature Sensor with Switches 7.5
QMX3.P30 Wall Temperature Sensor Only 7.5
QMX3.P34 Wall Temperature Sensor with Display 7.5
QMX3.P37 Wall Temperature Sensor with Switches and Display 10
QXM3.P40 Wall Temperature/RH/ Sensor without Display 7.5
QMX3.P70 Wall Temperature/RH/C02 Sensor 15
QMX3.P74 Wall Temperature/RH/C02 Sensor with Display 15
QMX3.P87 Fume Hood Operating Display Panel 8
QMX3.P88 Fume Hood Operating Display Panel (Thin) 8
JB260C23 Binary Input (4x) 10
JB510C23 Binary Output (2x Relay) 10
JB512C23 Switching Actuator (1x 20 A Relay) 10
JB513C23 Binary Output (3x Relay) 10
JB520C23 Solar Protection (1x Actuator) 10
JB521C23 Solar Protection (2x Actuator) 10
JB525C23 Universal 120V Dimmer 10
JB125C23
KNX Power Supply 80 mA at DC 2V
AC 120V, 50 through 60 Hz (maximum eight on Bus)
(80 … 640)