Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
146
| 231
125-3002
KNX PL-Link Connection
KNX PL-Link distances within the APOGEE Automation system are typically short and
not subject to large electrical noise. It is recommended to use 20 AWG solid copper
unshielded twisted pair cables; however, the drain wire must not be connected.
Substitute 18 AWG solid copper shielded twisted pair cable where long wire runs
make voltage drop a concern. Use CMP where plenum rating is required.
Fig. 91: Connecting KNX PL-Link.
Fig. 92: KNX PL-Link Device Termination.