Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
144
| 231
125-3002
Lab DXR power, signal and communications to two/four APS with
Actuator in IP54 box
Maximum cable distance between DXR enclosure and APS and Actuator limited
by 24 Vac
80 m (260 ft) on 14 AWG wire
50 m (164 ft) on 16 AWG wire
For IP54 splash proof box orientate power/signal and SCOM conduits facing down
Actuator cable run through side conduit connection
Signal cable from Lab DXR to APS Y and U
Dedicated 18 AWG twisted pair
Run in same 4 conductor twisted cable as 24 Vac
SCOM run in line topology from Lab DXR to each APS maximum cable length
800 m (2600 ft)
Two MSTP cables with reference wire
One data cable with two pairs using APS reference impedance in place of
reference wire
Fig. 89: DXR2.x17C... wiring of Sensor/Actuator with two ducts, central transformers, line topology for
SCOM.