BACnet DXR2 Room Automation Station
138
| 231
125-3002
Pressurized Rooms with Fume Hoods (Ethernet)
For Critical Environment DXRs in a pressurized space:
The DXR2.E controllers may be in a star configuration, a daisy chain configuration
or a daisy chain with loop back and RSTP.
The daisy chain may include up to 20 devices (room or fume hood).
All controllers in a pressurized space must be on a common switch.
Multiple pressurized spaces can be in the daisy chain and on the same switch.
If doing RSTP, loop back to the same switch. The standard DXR documentation
shows the loop back with different switches.
A single pressurized space may include up to 20 Fume Hoods (1 exhaust each),
and should not exceed 16 supply and extracts.
NOTE: DXR2.C handles 1 supply and 1 extract. DXR2.CX handles 2 supplies and
2 extracts.
The controller running the room HVAC coordination application should be a C (1
room segment) when more than two supply/extract tracking pair and 8 fume hoods
are in the pressurized space.
Lab DXR2 Networking Examples
Fig. 78: Lab DXR2 network - Daisy chain