BACnet DXR2 Room Automation Station
136
| 231
125-3002
Fig. 73: Lab MS/TP - Common Pressurized Space
Fig. 74: Lab MSTP – Combination Multi-room and Fume Hoods
Airflow communication network (F-COM)
On CET MS/TP automation stations (DXR2.M17x), the data collected over the F-COM
(flow communication) network communicates data related to air supplied and
exhausted in and out of the room, including supply terminal(s), extract terminal(s), and
fume hood(s). This separate, dedicated network is needed because the standard
BACnet MS/TP network is occupied with other network traffic. FCOM handles airflow
related data necessary for dynamic room pressurization changes.
Multiple fume hood flows are totaled by the CetRCtl group master object. The result is
displayed in the object for Room fume hood air volume flow (AirFlFhR) located in the
pressure control AF (CetAirFlTck11 or CetPFlCas11).
The following figure provides a simplified view of F-COM network only. The standard
BACnet MS/TP network wiring is not shown.