BACnet DXR2 Room Automation Station
125
-3002
135 | 231
Pressurized room with or without Fume Hoods (MSTP)
For Critical Environment DXRs in a pressurized space:
The DXR2M controllers should have their MSTP ports connected per 1.5 pair
recommendations, see MS/TP Connection [ 134].
DXR2.M17xx controllers have a second RS485 port called FCOM.
Each pressurized space will have its own FCOM bus. The FCOM ports of all
controllers in a pressurized space should be connected, including the DXR2 with
the room HVAC coordination application.
The number of DXR2M devices on FCOM is determined by the number of remote
room segments (CetRSegm). The maximum number is 5 remote room segments.
A single pressurized space may include up to 5 Fume Hoods (1 segment each) if
there are no remote room segments.
DXR2.M17C handles 1 room segment. DXR2.M17CX handles 2 room segments.
BACnet addresses for controllers in the pressurized space should be contiguous.
Max Master must be 30 or less.
The exception to the 5 remote segment limit is if the MSTP network is dedicated to
the single pressurized space, either with connection at a field panel or with a
router. In this case, the limit is 8. The BACnet addresses must be contiguous with
the max master set to the highest address, <= to 8.
Fig. 72: Lab MS/TP with Fume Hoods