Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
125
-3002
127 | 231
DXR2.E17C
Pin Description Terminal Module Channel
1, 2 Ethernet 2 x RJ45 interface for 2-port Ethernet switch
11, 12 KNX KNX connection +, -
31...41 inputs 10K Resistance input B1, B2 1 9…10
Universal input X1...X4 1 5…8
System neutral
Field supply AC 24 V for active sensors V~
Field supply DC 24 V for active sensors V+
USB USB interface
51...52 power 24V~ Power supply SELV / PELV AC 24 V ~
System neutral
61...65 inputs Digital input D1, D2, D3 1 1…3
System neutral
71...73 SCOM +, -
System neutral
81...86 triacs Switching output AC 24 V Y1...Y4 11 1…4
System neutral
91...98 analog
outputs
Positioning output DC 0...10 V Y10...Y40 21 1…4
System neutral
Field supply AC 24 V V~
Service Service button SVC
Display Operation LED RUN
Active communication LED SCOM