Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
126
| 231
125-3002
Terminal Symbol Description Modul
e
Channel
1, 2 Ethernet
2 x RJ45 interface for 2-port Ethernet switch
11, 12 KNX +, - KNX connection
31...41 inputs D1, D2 Digital input 1 1, 2
X1...X4 Universal input 1 5...8
System zero
V~ Field supply AC 24 V for active sensors
V+ Field supply DC 24 V for active sensors
USB
USB interface
51...52 power 24
V~
V~ Power SELV / PELV AC 24 V
System zero
61...72 Triacs Y1...Y8 Switching output AC 24 V 11 1...8
System zero
81...88 analog
outputs
Y10...Y40 Positioning output DC 0...10 V 21 1...4
System zero
V~ Field supply AC 24 V
Service SVC Service button
Display RUN Operation LED
9
20 05Z 5
DXR2.E18