Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
125
-3002
125 | 231
Analog Inputs (X1 X2)
Analog inputs are not suitable for operating lighting or blinds. Use the KNK PL-Link
push button devices.
Connection Terminals
IP
Terminal Symbol Description Modul
e
Channel
1, 2 Ethernet
2 x RJ45 interface for 2-port Ethernet switch
11, 12 KNX +, - KNX connection
31...36 inputs D1 Digital input 1 1
X1, X2 Universal input 1 5, 6
System zero
V~ Field supply AC 24 V for active sensors
USB
USB interface
51...52 power 24
V~
V~ Power SELV / PELV AC 24 V
System zero
61...69 Triacs Y1...Y6 Switching output AC 24 V 11 1...6
System zero
81...84 analog
outputs
Y10, Y20 Positioning output DC 0...10 V 21 1, 2
System zero
V~ Field supply AC 24 V
ΔP differential
pressure detector
P1+ Connected to the higher pressure 31 1
P1- Connected to the lower pressure 31 1
Service SVC Service button
Display RUN Operation LED
920 05Z 2
DXR2.E12P