Engineering Documentation

Table Of Contents
Chapter 4 Equipment Controllers
BACnet DXR2 Room Automation Station
124
| 231
125-3002
Engineering
Engineering [24 V] [Content Released]
Identification
Each device has a unique serial number to ensure efficient commissioning. It is
provided on the adhesive barcode label. The serial number can be read directly into
the engineering tool using a barcode reader.
Wiring
Wiring must be sufficiently insulated to the available rated voltage. Sizing and fusing of
the wiring depend on the connected load. See the section Wire Type Requirements
[ 121].
Triac Outputs AC 24V (Y1 Y8)
Individual Triac outputs may have a maximum load of 6 VA (heating up the device).
The following possibilities are permitted:
Multiple motorized actuators with a total of maximum 6 VA.
One (1) thermal actuator with 6 VA (0.25 A) start load in a cold state, controlled
using the algorithm PWM 0 through100%.
One (1) thermal actuator with 9 VA (0.37 A) start load each in a cold state,
controlled using the algorithm PWM 5 through 50%.
For transformer design (voltage drop off), each thermal actuator must be counted at
the full start load, since the Triac outputs can be freely controlled. The heating
sequence and cooling sequence are not normally active at the same time (exception:
downdraft compensation).
The total of the base load, bus power, field supply, and Triacs may not exceed 72 VA
(DXR2.E18P) or 70 VA (DXR2.M18P/T18P). The DXR2.E17C/M17C may not exceed
79VA. Power consumption is 96 VA with pulse width modulation.
See the section Power Trunk Layout [ 67].
NOTE: The DXR2.x17C and DXR2.x17CX have a maximum load of 12 VA per Triac.
For the DXR2… 24V variant, the high side switch Triacs (closed the contact at
AC 24V) are used. As a result, the VAV compact controllers GDB181.1E/3 or
GLB181.1E/3 can only be set to operating mode con using 0 through 10V.
DC Through 10V Outputs (Y10 Y40)
The DC 0 through 10V outputs supply maximum 1 mA.
AC 24V Supply for Field Devices (V~)
Actuators (valves, dampers) and active sensors are supplied directly by the device.
Separate AC 24V power supply is only required if field devices consume more than 12
VA (on DXR2.x11… and DXR2.x12…) or 18 VA (on DXR2.x18).
DC 24V Power Supply for Field Devices (V+), DXR2.x18 and
DXR2.x17… Only
Actuators (valves, dampers) and active sensors are supplied directly by the device. A
separate DC 24V field supply is only required if field devices use more than 2.4 Watts.
Digital Inputs (D1 D2)
Digital inputs are not suitable for operating lighting or blinds. Use the KNK PL-Link
push button devices.