Point Expansion or Conversion
AO-P Transducer
The AO-P Transducer converts field panel voltage output or current output to
pneumatic output.
Recommended maximum wiring runs for the AO-P Transducer Remote Mount (545-
208) and the AO-P Transducer Panel Mount (545-113) are listed in table AO-P
Transducer Remote Mount and Panel Mount Wiring Run Limitations.
AO-P Transducer Remote Mount and Panel Mount Wiring Run Limitations.
Circuit Type Class Wire Type
1)
Maximum Distance
24 Vac Power 2 No. 18 to 22 750 ft (230 m)
0 to 10 Vdc (Signal) 2 No. 18 to 22 TP 1000 ft (305 m)
0 to 5 Vdc (feedback) 2 No. 18 to 22 TP 1000 ft (305 m)
Digital Output 2 No. 18 to 22 1000 ft (305 m)
4 to 20 mA 2 No. 18 to 22 TP 1000 ft (305 m)
1)
See the Wire Specification Tables section in Chapter 1—Wiring for more information.
Power Source Requirements
Power Source Requirements for AO-P Transducer.
Product Input Voltage Line Frequency Maximum Power
AO-P Transducer 24 Vac 50/60 Hz 1 VA
AO-P Wiring Connections.
AO-P Transducer Wire Color Connection
Red (HK) 24 Vac
Black (N) Neutral
Yellow (+) 0 to 10 Vdc, or 4 to 20 mA (Signal +)
White (F) 0 to 5 Vdc (Feedback +)
Gray (I-) Signal/Feedback Negative (-)
Orange (A)
1)
DO (Dry Contact)
Orange (B)
1)
DO (Dry Contact)
1)
Together, the two orange wires make up the DO. These connections are optional. The DO
reports the position of the Hand-Auto switch:
- Open Contact=Auto Mode
- Closed Contact=Hand Mode