Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
PXC Compact Series Controller
116
| 231
125-3002
Digital Input, Dry Contacts; Not Supervised
Fig. 65: Connecting a Digital Input (Dry Contacts).
1) A single common may be used for all digital inputs.
2) Excitation equals 24 Vdc at 6 mA for 150 msec, then 1 mA. Must be stable for 100 msec.
3) Excitation equals 24 Vdc at 10 mA. Cannot be used for pulse accumulating.
4) Dry contact only. Does not require gold contacts.
5)
Solid state device must be rated for 30V minimum, with RDS on less than 1K ohms and RDS off greater than 100K
ohms.