Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
PXC Compact Series Controller
110
| 231
125-3002
Shared Ground Connections (PXC-36).
PXC Compact Series Wiring Diagrams
WARNING
All transformer or isolated power supply secondary neutrals requiring connection to
earth ground must be directly connected to an approved building earth ground
terminal located at the point termination module where the signal is terminated.
This is represented in the following diagrams by “E” at the earth ground symbol.
Point Type Specifics [Page Number]
Analog Input Internally powered, voltage or current, supervised [
111]
Externally powered, voltage or current, supervised [
111]
RTDs or Thermistors, supervised [
112]
Analog Output 0-10 Vdc, not supervised [
113]
0-20 mA, not supervised [
114]
Digital Input Dry contacts, not supervised [
116]
Pulse accumulating, not supervised [
117]
Using AI, Supervised – See the MEC wiring diagram [
162]
Digital Output Pulsed or latched, not supervised [
118]