Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
PXC Compact Series Controller
125
-3002
109 | 231
PXC-36 Supported Point Types.
Configurable Points Dedicated Points
Point Type Super Universal (X)
Points 1-6
Universal
Input/Output (U)
Points 7-24
Digital Input (DI)
Points 25-28
Digital Output (DO)
Points 29-36
Digital
Output
Binary/Digital Output
4)
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Requires an external relay.
5)
Sensor supply 24 Vdc, 4.8W
Compact Series Sensor Wiring
The PXC Compact uses a shared ground between sensors to reduce the number of
required terminal connections. The PXC Compact ground contacts are shared as
shown the following figures.
Shared Ground Connections (PXC-16 and PXC-24).