125-3002
Power Source Requirements
PXC Compact Power Source Requirements.
Product Input
Voltage
Line Frequency Maximum Power
1) 2)
PXC-16 24 Vac 50/60 Hz 18 VA
PXC-24 24 Vac 50/60 Hz 20 VA
PXC-36 24 Vac 50/60 Hz 35 VA
1)
The 24V wiring is Class 2.
2)
An external connection is provided for power at 24 Vdc at 50 mA per termination
(200 mA maximum all terminations) for external sensors.
WARNING
Install external supply line fusing in series with relay contacts and controlled
device.
Fuse type and value should be lowest required by control relay datasheet or
controlled device datasheet.
Failure to install fuse may result in damage to relay or device.
Analog Input Powered Devices
Approved sensors can be powered by the PXC Compact Series 24 Vdc Sensor
Supply.
Version 1 of the PXC-16 and PXC-24 support up to 100 mA. The Version 1 model
number format is PXC16-xxx.A or PXC24-xxx.A.
All versions of PXC-36 and Version 2 and later of the PXC-16 and PXC-24 support
200 mA. The Version 2 model number format is PXC16.2-xxx.A or PXC24.2-
xxx.A.
Sensors requiring more power must be powered by an external source.
The external source can be connected to the same 24 Vac line as the PX Series
Service Box power supply as long as it is only used to power low voltage devices
(less than 30 volts).
An external sensor supply must be connected to the same Building Earth Ground
as the PXC Compact
Analog Output Powered Devices
The PXC Compact does not provide actuator output power. See the PX Series
Service Box [ 81] section in this chapter.
Powering Options
One of the options for powering the PXC Compact, point blocks, and 24V devices is
the PX Series Service Box.
See PX Series Service Boxes [ 81] in this chapter for more information.