2-wire and 3-wire Active Input (Current); Supervised,
Super Universal Modules Only
B4 Active sensor with 24 Vdc supply
B5 Active sensor with 24 Vac supply
B6 Active sensor 4 to 20 mA (2 wire)
B7 Active sensor with external supply
(earth ground only at Service Box)
2-wire and 3-wire Active Input (Current); Supervised, Super Universal Modules Only.
Analog Ouput (Voltage or Current); Not Supervised,
Universal and Super Universal Modules
0-10 Vdc available on Universal and
Super Universal modules, points 1-8.
4-20 mA only available on Super
Universal modules, points 5-8.
Y1 Actuator with control input only
Y2 24 Vac internal
Y3 24 Vdc internal
Y4 24 Vac external
Analog Ouput (Voltage or Current); Not Supervised, Universal and Super Universal Modules.
PXC Compact Series Controller
NOTE:
UL-recognized wire (labeled with a backwards “RU”) is not field-installable. Use only
UL-listed wire.
For analog inputs, termination for shield is provided, if required. Termination for shield
is not provided for digital inputs. For more information, see the PXC Compact Series
wiring diagrams [ 110].