Universal Module Terminal Layout.
I/O Point
(1) (2) (3) (4) (5) (6) (7) (8)
Measuring Neutral (-)
1)
2 6 10 14 19 23 27 31
Input (+)
4 8 12 16 21 25 29 33
AC Actuator Supply Voltage
2)
Selected from: 7, 15, 24, 32
1)
All measuring/neutral terminals are connected in the plug-in I/O module, not in the terminal
base. When the I/O module is removed, there is no connection. The neutral of a digital input
can be connected to any neutral terminal on the same module. Several digital inputs can also
share a neutral terminal.
2)
All AC actuator supply voltage terminals are connected in the I/O module, not in the terminal
base. They are protected through the fuse on the TX-I/O Power Supply or P1 BIM.
Super Universal Module Terminal Layout.
I/O Point
(1) (2) (3) (4) (5)
1)
(6)
1)
(7)
1)
(8)
1)
Measuring Neutral (-)
2)
2 6 10 14 19 23 27 31
Input (+)
4 8 12 16 21 25 29 33
AC Actuator Supply Voltage
3)
Selected from: 7, 15, 24, 32
24 Vdc Sensor Supply Voltage
4)
Selected from: 3, 11, 20, 28
1)
0 to 20 mA output is available on points 5 through 8 only.
2)
All measuring/neutral terminals are connected in the plug-in I/O module, not in the terminal
base. When the I/O module is removed, there is no connection. The neutral of a digital input
can be connected to any neutral terminal on the same module. Several digital inputs can also
share a neutral terminal.
3)
All AC actuator supply voltage terminals are connected in the I/O module, not in the terminal
base. They are protected through the fuse on the TX-I/O Power Supply or P1 BIM.
4)
All 24 Vdc supply terminals are connected. They are overload protected in the module.
Digital Input, Dry Contacts; Not Supervised, Universal
and Super Universal Modules
K1 Status contact (N/O)
K2 Status contact (N/C)
K3 Pulsed accumulator
S5
Electronic switch (rated for 30V, 6 mA
for 150 ms, then 1 mA)
Digital Input, Dry Contacts; Not Supervised, Universal and Super Universal Modules.