Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
TX-I/O Product Range
100
| 231
125-3002
Digital Output Module Terminal Layout.
Output Point
(1) (2) (3) (4) (5) (6)
Common
3 9 15 20 26 32
N/O Contact
2 8 14 21 27 33
N/C Contact
4 10 16 19 25 31
For logical point types with several I/O points, do the following:
Always use adjacent I/O points.
Confine each logical point type to one module only.
Latched; Not Supervised, Digital Output Module
Q1 Switched load (NO contact)
Q2 Switched load (NC contact)
Latched; Not Supervised, Digital Output Module.
Pulsed; Not Supervised, Digital Output Module
Q1 Pulse-driven device (for example, a
stepping switch)
K1 Power contactor, self-latching
Pulsed; Not Supervised, Digital Output Module.