User Guide
Application MC
FLN Device and Network Set-up
76
Siemens Industry, Inc.
Kiosk Mode User Guide
A6V10455247
Building Technologies
2017-06-30
● (
Optional)
D3$# (the $# parameter is for Unit Vent applications only.) Since Unit
Vent applications contain several Control Diagrams you need to specify which
Control Diagram should display. Therefore, type
$# where # is the number of the
Control Diagram as specified in the
Application Guide
. For example, $2 would
display Control Diagram 2 (Control Diagram 1 is the default).
The following examples show correctly formatted
Description fields:
●
BUILDING1.FLOOR2.ROOM203$2
●
THOMAS_HALL..LOBBY$2
●
THOMAS_HALL..$2
●
KBuilding.Flr2.RM201
NOTE:
Only devices with correctly formatted description strings, which have been added to
the host field panel database, are added to the navigation tree.
The layout of the navigation tree is as follows:
Buildings
D1 (Suggestion – Building) - Required
D2 (Suggestion – Floor) - Optional
D3 (Suggestion – Room)
Device1
Device2
…
Device
n
Changing the Control Diagram in the Description
Property using WCIS
If the control diagram in the description of a Unit Vent controller is incorrect, and the
Unit Vent was already discovered by Application MC, you can change the description
to use a different control diagram.
NOTE:
The
Description field can also be changed using the BACnet Object Browser.
1. Connect to the PTEC with WCIS, either directly or through the room temperature
sensor.
2. Select Device > Device Properties.
3. Edit the Description field.
4. Reset the PTEC by selecting Reset and Reset App.
5. If necessary, log on to Application MC.
6. Click the Update Navigation Tree button.