User Guide
FIN Builder Graphics Tool
Using the FIN Builder Graphics Tool
18
Siemens Industry, Inc.
Kiosk Mode User Guide
A6V10455247
Building Technologies
2017-06-30
Adding an Alarm Grid Update Timer
1. Select the Timer component from the Controls palette and add it to your graphic.
You may want to place the component close to the Alarm Grid for readability.
The Timer will not be visible once the graphic is published.
2. In the Timer Properties, do the following:
– Change the Name of the Timer to
ALARM_GRID_TIMER.
– Verify that
AUTO_START is selected.
– Change the
INTERVAL to 60 seconds.
3. Select the Timer component, click the plus button to add a new Action, and
then select Timer > Refresh Point.