Installation Instructions
Document No. 586-136
Installation Instructions
December 17, 2003
Page 2 of 4 Siemens Building Technologies, Inc.
Figure 2. Spacing Requirements.
Installation
NOTE: Follow all safety regulations and local codes
when installing this equipment.
1. Determine the mounting location of the enclosure
using the spacing requirements shown in Figure 2.
See Figure 3 and Figure 4 for panel dimensions.
• Minimum spacing between the panel and any
obstruction is 5 inches (127 mm) to the left
(hinged side) and 5 inches (127 mm) to the
right (lock side) (see Figure 5).
• Maximum depth is 11 inches (279.4 mm) to
allow for door clearance.
2. Draw a level line 6 feet (1.8 m) above the floor on
the wall or surface where the enclosure will be
mounted.
3. Affix the adhesive-backed template flush with the
line drawn above.
4. Drill through the template at each marked location
to create the mounting holes.
5. Create three conduit entrances at the top of the
enclosure with a Greenlee punch:
a. Punch one entrance on the right for the power
supply.
b. Punch two entrances towards the center of
the panel for Class 2 and other wires.
6. Mount the panel to the wall. Check the enclosure
to be sure it is level.
NOTE: Separate knockouts should be used for high
voltage and low voltage wiring. Leave at least
a 2-inch (50.8 mm) space between the Class
2 and other wires in the panel.
7. Run conduit and pull wires into the panel. Be sure
to leave enough wire for future changes or
additions.
8. Label each wire.
9. Place the MEC layout sheet in the label pouch
inside the door.
The installation is now complete.
To install the Service Box and Modular Equipment
Controller, see the following Installation Instructions:
• 586-135 MEC Service Box
• 586-146 Modular Equipment Controller