User Guide

FLN Device and Network Set-up
Changing the Control Diagram in the Description Property using WCIS
8
A6V10574894
2017-06-30
The layout of the navigation tree is as follows:
Buildings
D1 (Suggestion Building) - Required
D2 (Suggestion Floor) - Optional
D3 (Suggestion Room)
Device1
Device2
Device
n
Changing the Control Diagram in the Description Property
using WCIS
If the control diagram in the description of a Unit Vent controller is incorrect, and the
Unit Vent was already discovered by Application MC, you can change the description
to use a different control diagram.
NOTE:
The
Description field can also be changed using the BACnet Object Browser.
1. Connect to the PTEC with WCIS, either directly or through the room temperature
sensor.
2. Select Device > Device Properties.
3. Edit the Description field.
4. Reset the PTEC by selecting Reset and Reset App.
5. If necessary, log on to Application MC.
6. Click the Update Navigation Tree button.
7. To display the correct control diagram, select the Unit Vent with the changed
description (even if it is already selected).
Deploying Application MC
Application MC is deployed by selecting
Deploy Application MC from the Tools menu in
Launch Pad. See the
Launch Pad User Guide
for more information.