Data Sheet for Product
Siemens Industry, Inc.
Page 5 of 19
Specifications
Dimensions:
Modular Equipment Controller
11.4" H × 9.5" W × 3.75" D
(289 mm × 241 mm × 95 mm)
Analog Point Expansion Module 6" H × 9.5" W × 3.75" D
(152 mm × 241 mm × 95mm)
Digital Point Expansion Module 6" H × 9.5" W × 3.75" D
(152 mm × 241mm × 95mm)
NEMA Type 1 Enclosures:
18” Utility Cabinet Enclosure 18" H × 14" W × 6" D
(457.2 mm × 356.6 mm × 152.4 mm)
19” Enclosure 19" H × 22" W × 5.75" D
(482.6 mm × 558.8 mm × 146.1 mm)
34” Enclosure 34" H × 22" W × 5.75" D
(863.6 mm × 558.8 mm × 146.1 mm)
Processor Motorola MPC - 1200EB, 1200EFB, 1200ELB 860T
Processor Clock Speed 48 MHz
Memory Size 64 MB RAM/8 MB Flash (72 MB Total)
Battery Backup of RAM 14 days typical (field replaceable, AA Alkaline)
A/D Resolution (analog in) 12 bits
D/A Resolution (analog out) 8 bits
Local Communication Interface RS-232 port
Network Communication Speed
Automation Level Network BACnet/IP ALN: 10/100 Base-T
Field Level Network P1 FLN or BACnet MS/TP FLN: 9600, 19200, 38400
L
ONWORKS FLN: 38.4 Kbps
Point Expansion Bus
38.4 Kbps
Voltage Requirements
Service Box, 115V
Service Box, 230V
Controller or Expansion Module
115 Vac +/- 15% @ 60 Hz +/- 5%
230 Vac +/- 15% @ 50/60 Hz +/- 5%
20 Vac to 30 Vac @ 47 Hz to 63 Hz
Power Consumption
Power Modular Equipment Controllers
Analog Point Expansion module 8AI
Analog Point Expansion module 4AI/4AO
Digital Point Expansion module 8DI/4DO
Digital Point Expansion module 4DI/4DO
50 VA
17 VA @ 24 Vac
14 VA @ 24 Vac
20 VA @ 24 Vac
17 VA @ 24 Vac
Enclosure Type NEMA 1
+32F to +120F
(0C to +49C)
Ambient Operating Environment
93% RH (Non-condensing)
Mounting Surface
Building Wall or Structural Member
UL 864 UUKL
ULC-C100 UUKL7
Agency Listings
UL 916 PAZX
FCC Compliance
Australian EMC Framework
European EMC Directive (CE)
European Low Voltage Directive (LVD)
Agency Compliance
BACnet Testing Laboratories (BTL) Certified