Data Sheet for Product
Siemens Industry, Inc.
Page 15 of 19
Command Object Type
Property_Identifier Supported Writable Required \ Optional
Object_Identifier Yes R
Object_Name Yes
R
Object_Type Yes R
Description Yes Yes O
Present_Value Yes Yes W
In_Process Yes R
All_Writes_Successful Yes R
Action Yes Yes R
Action _Text Yes Yes O
Device Object Type
Property_Identifier Supported Writable Required \ Optional
Object_Identifier Yes R
Object_Name Yes R
Object_Type Yes R
System_Status Yes R
Vendor_Name Yes R
Vendor_Identifier Yes R
Model_Name Yes R
Firmware_Revision Yes R
Application_Software_Version Yes R
Location Yes O
Description Yes O
Protocol_Version Yes R
Protocol_Revision Yes R
Protocol_Services_Supported Yes R
Protocol_Object_Types_Supported Yes R
Object_List Yes R
Max_APDU_Lenght_Accepted Yes R
Segmentation_Supported Yes R
Max_Segments_Supported Yes O
Local_Time Yes O
Local_Date Yes O
Daylight_Savings_Status Yes O
APDU_Segment_Timeout Yes O
APDU_Timeout Yes R
Number_Of_APDU_Retries Yes R
Device_Address_Binding Yes R
Database_Revision Yes R
Configuration_Files Yes O
Last_Restore_Time Yes O
Backup_Failure_Timeout Yes Yes O
Active_COV_Subscriptions Yes O