Data Sheet for Product

Siemens Industry, Inc.
Page 13 of 19
Binary Input Object Type
Property_Identifier Supported Writable Required \ Optional
Object_Identifier Yes R
Object_Name Yes
R
Object_Type Yes R
Present_Value Yes Yes R
Description Yes Yes O
Device_Type Yes
O
Status_Flags Yes R
Event_State Yes R
Reliability Yes O
Out_Of_Service Yes Yes R
Polarity Yes
R
Inactive_Text Yes O
Active_Text Yes O
Elapsed_Active_Time Yes Yes O
Time_Of_Active_Time_Reset Yes
O
Time_Delay Yes - Alarm O
Notification Class Yes - Alarm Yes O
Alarm_Value Yes - Alarm O
Event_Enable Yes - Alarm Yes O
Acked_Transitions Yes - Alarm
O
Notify_Type Yes - Alarm O
Event_Time_Stamps Yes - Alarm
O
Binary Output Object Type
Property_Identifier Supported Writable Required \ Optional
Object_Identifier Yes R
Object_Name Yes
R
Object_Type Yes R
Present_Value Yes Yes W
Description Yes Yes O
Device_Type Yes
O
Status_Flags Yes R
Event_State Yes R
Reliability Yes O
Out_Of_Service Yes R
Polarity Yes
R
Inactive_Text Yes O
Active_Text Yes O
Elapsed_Active_Time Yes Yes O
Time_Of_Active_Time_Reset Yes
O
Priority_Array Yes R
Relinquish_default Yes R