Data Sheet for Product
Siemens Industry, Inc.
Page 11 of 19
Object Attributes
O indicates that the property is optional, per the BACnet standard.
R indicates that the property is required to be present and readable using BACnet services.
Yes indicates that the property is required to be present, readable, and writable using BACnet services.
Analog Input Object Type
Property_Identifier Supported Writable Required \ Optional
Object_Identifier Yes R
Object_Name Yes
R
Object_Type Yes R
Present_Value Yes Yes R
Description Yes Yes O
Device_Type Yes O
Status_Flags Yes R
Event_State Yes R
Reliability Yes O
Out_Of_Service Yes Yes R
Units Yes Yes R
Resolution Yes
O
COV_Increment Yes Yes O
Time_Delay Yes - Alarm O
Notification Class Yes - Alarm Yes O
High_Limit Yes - Alarm Yes O
Low_Limit Yes - Alarm Yes O
Deadband Yes - Alarm O
Limit_Enable Yes - Alarm O
Event_Enable Yes - Alarm Yes O
Acked_Transitions Yes - Alarm
O
Notify_Type Yes - Alarm O
Event_Time_Stamps Yes - Alarm
O
Analog Output Object Type
Property_Identifier Supported Writable Required \ Optional
Object_Identifier Yes R
Object_Name Yes
R
Object_Type Yes R
Present_Value Yes Yes W
Description Yes Yes O
Device_Type Yes
O
Status_Flags Yes R
Event_State Yes R
Reliability Yes O
Out_Of_Service Yes R
Units Yes R