Data Sheet for Product
3/6
Building Technologies SYNERGYR
®
Control and billing system CE1N2803en
HVAC Products For service and replacement – system overview 04.01.2005
Ordering
When ordering, please give type references of the components required.
Fittings for the heat meters and the valve (ALG…), M-bus cable for the heat meter
(WFZ.MBUSSET), address plug set (PTG1…) and operating set (ARG30…) must be
ordered as separate items.
When ordering Siemens heat meters, the required set day must be stated.
Gerätekombinationen
SYNERGYR
®
components are designed for exclusive use with the SYNERGYR
®
sys-
tem.
In connection with the WRI80 interface, the following products can be used (also refer
to “Application example“):
• Zone control with VVP47 and SSP81, or VVP45 and SSB81
• Individual room control with AEK84 and STE21.1 / STE71.1
• M-bus heat meters
• Room units QAW10 / QAW20…
• Consumption meters with pulse output
• Contact for DHW heating
• Apartment pump via AEK84
The SYNERGYR
®
system can also be used in conjunction with heating controllers type
RVL4…, RVA…, RVP3…, or RVD2…
System components
Central control unit for data acquisition and data storage from the apartments and for
controlling and monitoring SYNERGYR
®
plant.
The OZW30 collects the consumption data acquired and stored in the apartment (heat
consumption and other data). A maximum of 96 apartments and 6 general meters with
pulse output can be connected.
The central unit acquires messages of operating states, actual values, interventions
and faults.
12-month storage and 2 freely selectable set days.
Readout of consumption data with memory card or via interface.
Menu-driven operation with operating cards and LCD.
Only with Eco and Comfort applications: With impact on room temperature control of
the apartments; load influence acting directly on the heating controller.
Windows software for remote readout of data and remote operation of SYNERGYR
®
central units.
Electronic control and heat meter interface. Acquires the room temperature via the
room temperature sensor connected to the room unit bus and controls the room tem-
perature through a valve, reads heat energy consumption from the connected Sie-
meca™ M-bus heat meter, acquires pulses from third-party devices, stores data and
communicates with other SYNERGYR
®
devices via the building bus.
The WRI80 facilitates maximum and minimum limitation of the volumetric flow, provides
frost protection for the apartment and performs the pump and valve kick at regular in-
tervals.
Provides control of an apartment pump, if required, and keeps the zone valve fully open
for the period of time there is external demand for DHW.
Central unit OZW30
Readout software
Control and heat me-
ter interface WRI80