User`s manual
Establishing a Connection
Description
Once your PC is set up, as described in Configuring Your PC, you are
ready to connect to an Advance Network Gateway (ANG_EN).
Getting Started
… read through this Chapter prior to performing any procedures.
Before You Begin
1. Ensure that the ANG_EN is not connected to the network by
removing the RJ-45 plug from connector (J6) located on the edge of
the Communications board; reference page
23.
2. Connect a standard 9-pin COM cable from the PC COM port you
designated when you configured your PC (see page
26; step 6.) to
the Configuration Port J2 located on the Communications Board
(Figure 2-7).
3. Turn on the AC power to the ANG_EN Power Supply board;
reference page
18.
Password Protection
All programs on the ANG_EN Communication board are password
protected. This insures the data integrity of all configuration data and
limits unwanted access of the User’s network. To access any of the
configuration or diagnostic information the user must log in using the
password.
A password name can consist of any combination of alphanumeric
characters. The alphanumeric name must have a minimum of five and a
maximum of twenty characters. The ANG_EN Communication board is
shipped from the factory with the word “password” entered as the
default password name.
The user can change the password name at any time. To do this login
using the current password then type: “password stand stand”. Where
the word stand is the new password entered twice to verify that it was
properly entered.
How to Change
Password
How to Log Out
You may log out or close the Configuration and Diagnostic program at
any time by typing logout. However, the Configuration and Diagnostic
program will automatically log you out after five minutes.
30 • Data Communications Setup 2000590-001