User`s manual

AC Power (Mains) Connections
ANG_EN Power
Supply
The ANG_EN Power Supply can accept 90-264 VAC, 47-63 Hz inputs
without the need for setting switches or jumpers.
Installation personnel shall adhere to all AC Power (Mains) Specification
requirements; see Chapter 1. Specifications, page
WARNING
3. Failure to do so,
and operating the equipment in a manner not specified, can impair the
safety protection provided by the equipment.
Instructions
Step Action
1. Shut off the primary AC Power Supply line to this location.
2. Open the front panel of the ANG_EN by loosening the four
captive screws located on each corner; use 4mm Allen
wrench.
3. Install a 15-Ampere circuit breaker, a disconnect switch or a
receptacle in the power supply line or a switched receptacle
near the ANG_EN unit to make sure the unit can be
completely separated from the power source. Label the
breaker or receptacle box to make sure that the circuit is
clearly identifiable.
4. If unit is equipped with conduit connection box, go to step 5.
If not, perform this step and go to step 7.
Remove wiring access plates from the units. Punch holes
as required for either conduit or cable gland connectors.
Install connectors and replace the plates.
Wall Mounted Units With Conduit Connection Box.
Remove the Conduit Connection Box cover by loosening
the 2 fastening screws.
5.
Wall Mounted Units With Conduit Connection Box. Drill
holes as required for either conduit or cable gland
connectors. Install connectors and replace the plate.
6.
18 Installation 2000590-001