User`s manual
80 •• Troubleshooting 2000591-001
DataNET Troubleshooting Guide, Continued
Verify the configuration parameters by connecting a PC serial port to the
ANG_DN Configuration Port, logging in, and typing config display.
local> config display
Config:
device ANG_DN
address ip 161.218.54.56
netmask 255.255.255.0
iproute 0.0.0.0
time server ip 0.0.0.0
address ethernet 00.c0.c9.00.d2.3b
device id 161.218.54.55
channel B
loop 1
unit 0
port1 Advance Data Hiway
port2 DataNet Copper
Verify the following:
1. That each ANG_DN board (ANCB) has a unique IP address.
2. That each ANG_DN board (ANCB) uses the same netmask.
3. That the iproute is either not used (0.0.0.0) or points to the address
of your network default router (see your network administrator).
4. That the device id is unique per DataNET device and the same for
both ANCB boards. The Device ID is the DataNET address of the
ANG_DN itself. Therefore both sides must use the same address.
Typically the Device ID is set to the same address as the Channel A
IP address.
5. The channel entry must be unique to each ANG_DN board (ANCB)
and must be either a or b.
6. The DH Loop must be the same on both ANG_DN boards (ANCB)
and the allowable range is Loop # (1-8).
7. The DH Unit must be the same on both ANG_DN boards (ANCB).
The allowable ANG_DN unit range is Unit # (0-31).
Configuration
Parameter Errors
More Checks