User`s manual

48 Data Communications Setup 2000591-001
Setting Network Address & Loop and Unit Numbers, Continued
Parameters are temporarily saved in RAM after being entered. However,
parameters are not saved into long term storage (Flash) until you type
‘reset’.
2. Designate the ANCB you are connected to as Channel A, at the Lo-
cal > prompt type: config channel
3. To configure the ANG_DN IP address, at the Local > prompt type:
config address ip xxx.xxx.xxx.xxx
Where xxx.xxx.xxx.xxx should be replaced with the 12 digit unique
network address. See Assigning an IP (Internet Protocol) Address
page 50.
4. Press Enter.
5. To save your entry, at the Local > prompt type: reset
6. To configure the ANG_DN subnetmask, at the local > prompt type:
config netmask xxx.xxx.xxx.xxx
Where xxx.xxx.xxx.xxx is the subnet mask for your network. Typi-
cally, this would be 255.255.0.0 or 255.255.255.0.
7. To configure the device id, at the Local > prompt type: config device
id xxx.xxx.xxx.xxx
8. Where xxx.xxx.xxx.xxx is typically the IP Address of Hub ‘A’.
9. Press Enter.
10. Press Enter, and save your entry by typing at the local > prompt:
reset.
11. To configure the ANG_DN Loop number, at the local > prompt type:
config loop x
12. Where x is a number in the range from 1 - 8 depending on the ADH
Loop number of the Units to be connected directly to the ANG_EN
ADH bus.
13. Press Enter, and save your entry by typing at the local > prompt:
reset
Learning Hint