User`s manual
2000591-001 Installation •• 31
DataNET Connections
The DataNET ports can accept copper or fiber optic cables. All connec-
tions are made to connectors located on each ANCB module.
If the unit is to be installed in an existing Data Hiway installation the ex-
isting Data Hiway wiring can be used.
The ANG enclosure houses two identical ANCB modules. Each ANCB
provides either a channel A or B channel network interface for one Data
Hiway channel and one DataNET channel.
An internal Ethernet cross-link connection via the Ethernet 10Base2
(BNC) port provides the communication link between the two modules.
Each module to be configured as Channel A or Channel B
and with different IP Addresses
ANCB
Cross Link Cable
PC COM
Ports
IF you are wiring for … THEN go to …
DataNET Copper Connections 32
DataNET Fiber Optic Cable Connections 34
Description
Channel Designation
and IP Address
Instructions