2000591-001 Installation 29
Data Hiway Connections, Continued
For technical information on the Data Hiway refer to Appendix A in the
Optichrom Advance Library Set, Volume 2, Board Installation and Strap-
ping Manual.
Step Action
1. Turn off AC Power (Mains) to the ANG. Turn off AC Power
(Mains) to the ANG.
WARNING
Placing the Power Supply Assembly toggle ON/OFF switch
to OFF does not remove the main voltage to the unit. To
remove all input power to the unit, the external AC Power
(Mains) to the unit needs to be shut off.
2. Route the Data Hiway cable to the ANG_DN in accordance
with national or local electrical codes and regulations via
the holes drilled in the access plate; see Figure 2-1.
To make the Data Hiway connections easier we have made the Data
Hiway port connector a removable connector. Simply grasp the top por-
tion of the connector and pull it straight out from the base connector.
Do not plug-in the wired Data Hiway connector until you have set the
loop and unit number; see Chapter 3. Data Communications Setup.
3. Designate which ANCB will be Channel A and which will be
Channel B. We suggest the right module be channel A.
4. Locate the Channel A, Port 1 connector. To make the con-
nections easier the connector comes apart. Simply loosen
the two recessed captive screws, grasp the top portion of
the connector and pull it straight out from the base con-
nector.
5. Loosen the top wire retaining screws from the removed
connector. Strip the insulation ¼ -inch back from each of
the connector leads.
More Information
Instructions
Installation Note
CAUTION