Data Hiway Connections
This section provides instructions for connecting the ANG_DN to an ex-
isting Data Hiway.
The DataNET Gateway unit consists of two ANCB boards. One ANCB
board is configured as the channel A board and the other as the Channel
B board. The ADH Channel is connected to Port 1 while the DataNET
Channel is connected to port 2, see page 48, step 2.
Data Hiway
Port 1 Connections
Pin 1-ADH-A+
Pin 2-ADH-A-
Pin 3- Ground
Pin 1
The Advance Data Hiway requires a low capacitance, twin axial, 150-
ohm cable. The cable can be purchased from Siemens Applied Automa-
tion. See the table below for ordering the correct cable:
Dual Channel Installation Standard Oval Cable
Siemens Applied Automation
P/N 1681000-003
(Belden P/N SSD1743)
Dual Channel Installation Used for larger radius bends
Siemens Applied Automation
P/N 1686002-002
(Alpha P/N 516689)
Single Channel Installation Siemens Applied Automation
P/N 1686002-001
(Belden 9182, Alpha P/N 9283,
Manhattan P/N 39240)
Description
Figure 2-6. Data
Hiway Connector
Data Hiway Cable