Site Wiring Requirements, Continued
Use approved flexible non-metallic conduit wiring method. Conduit may
contain multiple cables. For CE installations use only cable gland wiring
method.
Cable Type: Recommend Belden 9182 or equivalent. Other cables with
individually shielded pairs can be used, but decreased distance is al-
lowed
The DataNET channel connections can be either copper wire or fiber
optic cable. The wiring method and cable type for DataNET is dependent
upon the site requirements.
See Page 22, CE Installations
Use approved Conduit wiring method. Conduit may contain multiple ca-
bles. Adhere to all Federal and local electrical code requirements.
Cable Type: Duplex fiber, 62.5/125 micron; see Table 2-1.
Connection: Type ST fiber connectors. Connect these to the appropriate
transmitter and receiver ports for the respective channel.
Use Cable Gland wiring method. Each cable gland allows entry of one
duplex fiber cable.
Cable Type: Duplex fiber, 62.5/125 micron.
Connections: Type ST fiber connectors. Connect these to the appropri-
ate transmitter and receiver ports for the respective channel.
Use approved flexible non-metallic conduit. Conduit may contain multiple
cables. Conduit may contain multiple. This method is suitable for CE in-
stallations.
Cable Type: Duplex fiber, 62.5/125 micron.
Connection: Type ST fiber connectors. Connect these to the appropriate
transmitter and receiver ports for the respective channel.