User`s manual

2000591-001 Installation 19
Site Wiring Requirements, Continued
The DataNET channel connections can be either copper wire or fiber
optic cable. The wiring method and cable type for DataNET is dependent
upon the site requirements. For cable requirements see Table 2-1.
The following Table should be used when evaluating or selecting cable
for an existing or new DataNET installation.
Cable Type Vendors & P/N Installation Notes
Fiber Optic
MM 62.5/125; 4 Fiber
Conductors Required
for TX/RX Redun-
dancy
SAA P/N 1270002-002
Industry Available from
Multiple Vendors
New Installation as
an alternative to
copper cable
Max distance from
Analyzer to ANG or
between Hubs
1520 meters (5000
ft)
2- Conductor Copper
Wire
SAA P/N 1686002-001
Belden P/N 9182
For
Belden Armored Cable
order
SAA P/N 1680000-002
Recommended for
Single Channel
Max distance from
Analyzer to ANG or
between Hubs
1520 meters (5000
ft)
4-Conductor Copper
Wire
SAA P/N 1681000-003
Belden P/N SSD1743
Recommended for
Dual Channel
Max distance from
Analyzer to ANG or
between Hubs
1520 meters (5000
ft)
DataNET Channels
Table 2-1.
Recommended DataNET
Cable