User`s manual

2000591-001 Introduction 5
ANG_DN Specifications, Continued
Ambient Installation
Conditions
Operation: -18° to +50°C (0° to 122°F)
0-99% relative humidity (non-condensing) maximum
0-75% relative humidity year-round average
(Purge with dry air or nitrogen if required in tropical conditions.)
Must not be exposed to direct sunlight.
Must be protected from rain.
Storage and Transport: -25° to +65°C
Power Nominal: 115 Vac / 230 Vac (universal input)
Tolerance: 85-140 Vac or 185-250 Vac; 47-63 Hz
300 watts
Power line protection: G fuse element per IEC 127-2, 4 A rating, slow-
blow
Power wiring in field made to screw terminals on two part connectors;
16 AWG (1.5 mm) or smaller power wiring is accepted; must conform
to local installation codes and requirements. If conformance to CE
certified installation requirements is required, power cable must be
shielded or installed in conduit.
Dual Communication
Modules
Redundant system consisting of two identical modules. Each module
consists of universal power supply and Advance Communications
Board (ANCB).
Protocol and Addressing Open Systems standard TCP/IP protocol and addressing (Transmis-
sion Control Protocol/Internet Protocol); Full Class A, B and C ad-
dresses and subnet masking supported
Wiring Connections
Two part connectors with screw-terminals provided for AC power
connection
Two part connectors with screw-terminals provided for cable con-
nection
Fiber Optic Coupler for Fiber Optic Connections