Gewinde-PICV
Typische Anwendungen Stellantriebe Datenblatt 4,5 mm 2,5 mm
– Heizkörper
– Kühldecke
– Ventilatorkonvektor
RTN..
STA..
SSA..
N2111
N4884
N4893
100 N 100 N
Betriebsspannung
Stellsignal Stellzeit [s]
AC 230 V
2-Punkt 210 STA23
3-Punkt 150 SSA31
AC 24 V
3-Punkt 150 SSA81
0...10 V 270
1)
STA63
AC/DC 24 V
2-Punkt / PDM 270 STA73
0...10 V 34 SSA61
RTN51
RTN71
RTN81
PN 10 1...90 °C DIN
DN
Rp/R
[Zoll]
[l/h]
Nenn
2)
[l/h]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
Datenblatt N2185
VPD110A-..
2)
10 Rp/R ⅜ 25…318 45 90 145 6
3)
200 8
3)
200 10
3)
200
VPD115A-.. 15 Rp/R ½ 25…318 45 90
145
6
3)
200 8
3)
200 10
3)
200
VPD110B-200 10 Rp/R ⅜ 95…483 200 20 200 20 200 20 200
VPD115B-200 15 Rp/R ½ 95…483 200 20 200 20 200 20 200
VPE110A-.. 10 Rp/R ⅜ 25…318 45 90 145 6
3)
200 8
3)
200 10
3)
200
VPE115A-.. 15 Rp/R ½ 25…318 45 90
145
6
3)
200 8
3)
200 10
3)
200
VPE110B-200 10 Rp/R ⅜ 95…483 200 20 200 20 200 20 200
VPE115B-200 15 Rp/R ½ 95…483 200 20 200 20 200 20 200
Typische Anwendungen Stellantriebe Datenblatt 4,5 mm 2,5 / 5 mm 15 mm
Heizgruppen
Lüftungs- und Klima-
anlagen
Kühldecke
VVS/VAV
Ventilatorkonvektor
Zonenregelung
STA..
SSA..
SAY..P..
N4884
N4893
A6V10628469
100 N 100 N 200 N
Betriebsspannung
Stellsignal
Stellzeit [s]
STA SSA SAY
AC 230 V 3-Punkt
150/300 30
SSA31 SAY31P03
2-Punkt 210
STA23
AC 24 V
0...10 V 270
1)
STA63
AC/DC 24 V 3-Punkt
150/300 30
SSA81 SAY81P03
(SSA81: AC 24 V)
2-Punkt/PDM 270
STA73
0...10 V
34/70 30
SSA61/SSA61EP SAY61P03
Modbus
30
SAY61P03/MO
PN 25 1...120 °C Ohne Messnippel Mit Messnippel
DN
G
[Zoll]
min
[l/h]
100
[l/h]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
Datenblatt N4855
VPP46.10L0.2 VPP46.10L0.2Q 10 ½ 30 200 16 600 16 600
VPP46.10L0.4 VPP46.10L0.4Q
10 ½ 65 333 16 600
10 ½ 65 370
16 600
VPP46.15L0.2 VPP46.15L0.2Q 15 ¾ 30 200 19 600 19 600
VPP46.15L0.6 VPP46.15L0.6Q 15 ¾ 100 575 19 600 19 600
VPP46.20F1.4 VPP46.20F1.4Q
20 1 200 1190 22 600
20 1 220 1330
22 600
VPP46.25F1.8 VPP46.25F1.8Q
25 1 ¼ 204 1470 39 600
25 1 ¼ 250 1800
39 600
VPP46.32F4 VPP46.32F4Q
32 1 ½ 450 3270 28 600
32 1 ½ 550 4001
28 600
PN 25 1...120 °C Ohne Messnippel Mit Messnippel
DN
Rp
[Zoll]
min
[l/h]
100
[l/h]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
∆p
min
[kPa]
∆p
max
[kPa]
Datenblatt N4855
VPI46.15L0.2 VPI46.15L0.2Q 15 ½ 30 200 19 600 19 600
VPI46.15L0.6 VPI46.15L0.6Q 15 ½ 100 575 19 600 19 600
VPI46.20F1.4 VPI46.20F1.4Q
20 ¾ 200 1190 22 600
20 ¾ 220 1330
22 600
VPI46.25F1.8 VPI46.25F1.8Q
25 1 ¼ 204 1470 39 600
25 1 ¼ 250 1800
39 600
VPI46.32F4 VPI46.32F4Q
32 1 ½ 450 3270 28 600
32 1 ½ 550 4001
28 600
VPI46.40F9.5Q 40 1 ½ 1370 9500
25 600
VPI46.50F12Q 50 2 1400 11500
36 600
1)
Im Regelbetrieb (Aufheizphase) min. Laufzeit ca. 30 s/mm
2)
.. =
Nenn
einsetzen;
Nenn
= Werkseinstellung = Volumendurchuss bei 0,5 mm Hub, bzw. Merkzahl 3 der Voreinstellung
3)
Δp
min
gilt jeweils für
Nenn
45 / 90 / 145 l/h; VPP46.. / VPI46..: Δp
min
ist für
100
. Für kleinere Volumenströme nden Sie im Datenblatt.