User Manual

18
PN 40 -25...220 °C
DN
k
vs
[m
3
/h]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
Datenblatt A6V11459527
VVF63.50-40K 50 36 1500 4000 2000
VVF63.65-63K 65 63 4000 2000
VVF63.80-100K 80 100 4000 2000
VVF63.100-150K 100 150 4000 2000
VVF63.125-220K 125 220 4000 2000
VVF63.150-315K 150 315 4000 2000
PN 40 -25...220 °C
DN
k
vs
[m
3
/h]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
∆p
s
[kPa]
∆p
max
[kPa]
Datenblatt A6V11459527
VXF63.15-1.6 15 1,6 2000 200 2000 200
VXF63.15-2.5 15 2,5 2000 200 2000 200
VXF63.15-4 15 4 2000 200 2000 200
VXF63.20-6.3 20 6,3 2000 200 2000 200
VXF63.25-6.3 25 6,3 2000 200 2000 200
VXF63.25-10 25 10 2000 200 2000 200
VXF63.32-16 32 16 1100 200 2000 200
VXF63.40-16 40 16 650 200 2000 200
VXF63.40-25 40 25 650 200 2000 200
VXF63.50-31.5 50 31,5 400 200 1150 200
VXF63.65-50 65 50 650 200
VXF63.80-80 80 80 400 200
VXF63.100-125 100 125 250 150
VXF63.125-200 125 200 160 100
VXF63.150-315 150 315 100 70
Flansch-Hubventile
Typische Anwendungen Stellantriebe Datenblatt
Notstell-
funktion [s]
20 mm 40 mm
Fernwärmeanlagen
Kesselanlagen
Kälteanlagen
– Warmwasser
Heizgruppen
Lüftungs- und Klima-
anlagen
SKD..
SKB..
SKC..
N4561
N4564
N4566
1000 N
2800 N 2800 N
Betriebs-
spannung
Stellsignal
Stellzeit [s]
SKD SKB/C
SKD
SKB/C
AC 230 V
3-Punkt 120 120 SKD32.50 SKB32.50 SKC32.60
3-Punkt 120 120 8
10/18
SKD32.51 SKB32.51 SKC32.61
3-Punkt 30 8 SKD32.21
AC 24 V
3-Punkt 120 120 SKD82.50 SKB82.50 SKC82.60
3-Punkt 120 120 8
10/18
SKD82.51 SKB82.51 SKC82.61
0...10 V, 4...20 mA 30 120 SKD60 SKB60 SKC60
0...10 V, 4...20 mA 30 120 15
10/20
SKD62 SKB62 SKC62
Modbus 30 120 SKD62/MO SKB62/MO SKC62/MO