User Manual
11
Threaded globe valves
Typical applications Actuators Data sheet
– Radiators RTN..
N2111
RTN51/RTN51G RTN71 RTN81
PN 10 1...120 °C DIN NF
DN
Rp/R
[Inch]
k
v
[m
3
/h]
∆p
max
[kPa]
∆p
max
[kPa]
∆p
max
[kPa]
Data sheet N2105 N2106
VDN110 VDN210 10 Rp/R ⅜ 0.09…0.63 60 60 60
VDN115 VDN215 15 Rp/R ½ 0.10…0.89 60 60 60
VDN120 VDN220 20 Rp/R ¾ 0.31…1.41 60 60 60
VEN110 VEN210 10 Rp/R ⅜ 0.09…0.63 60 60 60
VEN115 VEN215 15 Rp/R ½ 0.10…0.89 60 60 60
VEN120 VEN220 20 Rp/R ¾ 0.31…1.41 60 60 60
– VUN210 10 Rp/R ⅜ 0.14...0.60 60 60 60
– VUN215 15 Rp/R ½ 0.13...0.77 60 60 60
PN 10 1...110 °C
DN
Rp/R
[Inch]
k
v
[l/h]
∆p
max
[kPa]
∆p
max
[kPa]
Data sheet N2103
VD115CLC 15 Rp/R ½ 0.25...1.9 150 150
VD120CLC 20 Rp/R ¾ 0.25...2.6 150 150
VD125CLC 25 Rp/R 1 0.25...2.6 150 150
Typical applications Actuators Data sheet 4.5 mm 2.5 mm 4.5 mm
– Radiators STA..
SSA..
N4884
N4893
100 N
100 N 90 N
Operating voltage
Positioning
signal
Positioning time [s]
AC 230 V
2-position 210 STA23 – STA23HD
1)
3-position 150 – SSA31 –
AC 24 V
3-position 150 – SSA81 –
0...10 V 270
2)
STA63 – –
AC/DC 24 V
2-position/PDM 270 STA73 – STA73HD
1)
0...10 V 34 – SSA61 –
Normally Open / Normally Closed (for radiator valves) NC – NC
Threaded globe valves
Typical applications Actuators Data sheet 4.5 mm 2.5 mm
– Chilled ceilings STA..
SSA..
N4884
N4893
100 N
100 N
Operating voltage
Positioning
signal
Positioning time [s]
AC 230 V
2-position 210 STA23 –
3-position 150 – SSA31
AC 24 V
3-position 150 – SSA81
0...10 V 270
2)
STA63 –
AC/DC 24 V
2-position/PDM 270 STA73 –
0...10 V 34 – SSA61
Normally Open / Normally Closed (for radiator valves) NC –
Presettings for radiator valves VEN.., VDN.., VUN..
k
v
values [m
3
/h] at the different preadjusted positions (XP = 2K)
Control range with electromotoric
and electrothermic actuators
SSA.., STA..
n n n n n n
–
Control range with thermostatic
head RTN..
n n n n n n n
Reference numbers for preadjustment 1 2 3 4 5 N
N (k
vs
)
VDN110/VDN210/VEN110/VEN210 0.072 0.17 0.24 0.28 0.37 0.43 0.63
VDN115/VDN215/VEN115/VEN215 0.07 0.17 0.28 0.36 0.45 0.50 0.89
VDN120/VDN220/VEN120/VEN220 0.22 0.35 0.44 0.52 0.60 0.71 1.41
VUN210 0.14 0,26 0.34 0.39 0.40 0.43 0.60
VUN215
0.13 0.22 0.30 0.39 0.45 0.50 0.77
1)
Optimized for oor heating systems
2)
In control mode (warm-up time) min. running time approx. 30 s/mm
k
v
= nominal ow rate of cold water (5...30 °C) through the valve at the respective stroke and a differential pressure of 100 kPa (1 bar)
The selected k
v
values of the radiator valves can be easily and precisely set on the valve head in 5 steps + N (fully open).